Solenttech Inverter Chargers
- Pure Sinewave Inverter range from 1300W to
3500W
- 4 Stage Fully Automatic Charger adjustable
from 0-55A
- Optional Built-in Solar Charge controller
- Optional Remote Control
- 2 Year Warranty
| Inverter |
PM1500SL |
PM1500SL |
PM3000SL |
PM3000SL |
| Nominal battery voltage |
12V |
24V |
12V |
24V |
| Input voltage range |
9.5- 16V |
19 - 32V |
9.5- 16V |
19 - 32V |
| Nominal power |
1500 W |
1500 W |
3000 W |
3000 W |
| Maximum power load 30 min. P30 |
1700 W |
1700 W |
3500 W |
3500 W |
| Maximum load |
up
to short circuit |
| Maximum asymmetric load |
up
to nominal power |
| Load Power Factor Range |
0.1
to 1 W |
| Maximum effciency |
85-90% |
85-90% |
85-90% |
85-90% |
| Power saving function-Enable/Disable |
yes |
yes |
yes |
yes |
| Output voltage |
230
Vac (0 / - 10%) |
| Output frequency |
50
Hz + 0.05% |
| Overload and
short circuit protection |
Automatic
disconnecting with 5 time restart attempt |
| Overheat protection |
Acoustic
warning before shut-off with automatic restart |
| PDF file |
See PDF file |
See PDF file |
See PDF file |
See PDF file |
| Battery Charger
|
PM1500SL |
PM1500SL |
PM3000SL |
PM3000SL |
| Technical Data |
| Charging current adjustable |
0 - 50 A |
0 - 35 A |
0 - 100A |
0 - 70 A |
AC Input Power Sharing Control
(Power Sharing) |
0 - 15 A |
0 - 15 A |
0 - 15 A |
0 - 15 A |
| Maximum input voltage |
265
Vac,350v peak |
| Minimum input voltage |
Adjustable
threshold from 150 to 230 Vac |
| Input frequency |
45
- 63 Hz |
| Power Factor
Correction (PFC) |
EN
61000-3-2 |
| PDF file |
See PDF file |
See PDF file |
See PDF file |
See PDF file |
| Technical Data |
PM1500SL |
PM1500SL |
PM3000SL |
PM3000SL |
| General Data |
Maximum Charging Current
|
30A |
| Solar Charge Regulator |
25v/font> |
45v |
25v |
45v |
| Transfer time UPS Mode |
<
20 ms |
| Weight |
20 kg |
20 kg |
28 kg |
28 kg |
| Dimensions L x W x H (mm) |
385 x 280 x 190 |
385 x 280 x 190 |
550 x 280 x 190 |
550 x 280 x 190 |
| IP protection index |
IP
20 |
| EEC conformity |
EN50081
I/II, EN 55014 - EN 55022, EN 61000-3-2 IEC 801 I/II/III/IV,
CEI 555, IEC 1000-3-2, LVD 73/23/EEC |
| Working range |
-20
to 55ºC |
| Ventilation |
from
45ºC-over 75C will cause trip |
| Acoustic level
without / with ventilation |
<
10 dB / <35dB |
| Recommended battery capacity (C10) |
>
5 x Pnom / Unom |
| Warranty |
2
years |
| PDF file |
See PDF file |
See PDF file |
See PDF file |
See PDF file |
| General Data |
| AC by pass time UPS mode-20ms max |
| Minimum input voltage UPS mode-Adjustable 150-230vac |
| |
|
Studer Compact Inverter Charger

- Pure Sinewave Inverter range from 1300W to
3500W
- 4 Stage Fully Automatic Charger adjustable
from 0-55A
- Optional Built-in Solar Charge controller
- Optional Remote Control
- High Quality 2 Year Warranty
Technical Data
| Inverter |
C 1600-12 |
C 2600-24 |
C4000-48 |
| Nominal battery voltage |
12V |
24V |
48V |
| Input voltage range |
9.5 - 16 V |
19 - 32 V |
38 - 64 V |
| Nominal power |
1300 W |
2300 W |
3500 W |
| Maximum power load 30 min. P30 |
1600 W |
2600 W |
4100 W |
| Maximum load |
up
to short circuit |
| Maximum asymmetric load |
up
to Pnom |
| Standby Adjustment |
1
to 25 W |
| Maximum effciency |
94% |
95% |
95% |
| Consumption OFF/ Standby/ON |
0.5 / 0.6 / 6 W |
0.8 / 0.9 / 9 W |
1.2 / 1.4 / 12 W |
| Output voltage |
230
Vac (0 / - 10%) |
| Output frequency crystal controlled |
50
Hz + 0.05% |
| Overload and
short circuit protection |
Automatic
disconnecting with 3 time restart attempt |
| Overheat protection |
Acoustic
warning before shut-off with automatic restart |
| PDF file |
See PDF file. |
See PDF file. |
See PDF file. |
| Technical Data
|
C 1600-12 |
C 2600-24 |
C4000-48 |
| Battery charger (4 STEP) I-U-Uo-Equalise
(every 25 cycles) |
| Charging current adjustable |
0 - 55 A |
0 - 55 A |
0 - 50 A |
Input current balance adjustable
(Power Sharing) |
1 - 16 A |
1 - 16 A |
1 - 16 A |
| Maximum input voltage |
265
Vac |
| Minimum input voltage |
Adjustable
threshold from 150 to 230 Vac |
| Input frequency |
45
- 65 Hz |
| Power Factor
Correction (PFC) |
EN
61000-3-2 |
| PDF file |
See PDF file. |
See PDF file. |
See PDF file. |
| Technical Data |
C 1600-12 |
C 2600-24 |
C4000-48 |
| Optional solar charger (4 stages) |
Maximum PV open circuit
voltage (V) |
25 V |
45 V |
90 V |
Maximum charge
current (A) |
30 A |
30 A |
20 A |
Working principle:
I-U-Uo-Equalise (every 25 cycles) |
Shunt |
Shunt |
Shunt |
| PDF file |
See PDF file. |
See PDF file. |
See PDF file. |
| Technical Data |
C 1600-12 |
C 2600-24 |
C4000-48 |
| General Data |
Multifunction contact -
potential free (3 points) |
16
A - 250 Vac |
| Max. current on transfer relay |
15 A / 3.5 kVA |
15 A / 3.5 kVA |
15 A / 3.5 kVA |
| Transfer time |
<
20 ms |
| Weight |
16.0 kg |
17.1 kg |
29.4 kg |
| Dimensions L x W x H (mm) |
480 x 215 x 124 |
480 x 215 x 124 |
670 x 215 x 124 |
| IP protection index |
IP 20 / IP 23 with top cover |
| EEC conformity |
EN50081
I/II, EN 55014 - EN 55022, EN 61000-3-2 IEC 801 I/II/III/IV,
CEI 555, IEC 1000-3-2, LVD 73/23/EEC |
| Working range |
-20
to 55ºC |
| Ventilation |
from
45ºC |
Acoustic level
without
/ with ventilation |
<
10 dB / <35dB |
| Warranty |
2
years |
| PDF file |
See PDF file. |
See PDF file. |
See PDF file. |
| Optional Extras for C Range |
| Solar charger |
| Remote control |
| Remote power sharing |
| IP-23 top cover |
| AC cable cover |
| Battery temperature
sensor |
Studer HPC Inverter Charger

- Pure Sinewave Inverter range from 2500W to
7000W
- 4 Stage Fully Automatic Charger adjustable
from 0-110A
- Optional Remote Control
- High Quality 2 Year Warranty
Technical Data
| Inverter |
HPC 2800-12 |
HPC 4400-24 |
HPC 6000-48 |
HPC 8000-48 |
| Nominal battery voltage |
12V |
24V |
48V |
48V |
| Input voltage range |
9.5 - 17 V |
9.5 - 34 V |
38 - 68 V |
38 - 68 V |
| Nominal power |
2500 W |
4000 W |
5000 W |
7000 W |
| Maximum power load 30 min. P30 |
2800 W |
4500 W |
6000 W |
8000 W |
| Maximum load |
up
to short circuit |
| Maximum asymmetric load |
up
to Pnom |
| Standby Adjustment |
1
to 25 W |
| Maximum effciency |
93% |
94% |
96% |
96% |
| Consumption OFF/ Standby/ON |
1.4 / 1.8 / 10 W |
1.7 / 2 / 16 W |
2 / 2.5 / 18 W |
2 / 3 / 25 W |
| Output voltage |
230
Vac (0 / - 10%) |
| Output frequency crystal controlled |
50
Hz + 0.05% |
| Overload and
short circuit protection |
Automatic
disconnecting with 3 time restart attempt |
| Overheat protection |
Acoustic
warning before shut-off with automatic restart |
| PDF file |
See PDF file |
See PDF file |
See PDF file |
See PDF file |
| Technical Data
|
HPC 2800-12 |
HPC 4400-24 |
HPC 6000-48 |
HPC 8000-48 |
| Battery charger (4 STEP) I-U-Uo-Equalise
(every 25 cycles) |
| Charging current adjustable |
0 - 110 A |
0 - 100 A |
0 - 70 A |
0 - 90 A |
Input current balance adjustable
(Power Sharing) |
1 - 30 A |
1 - 30 A |
1 - 30 A |
1 - 50 A |
| Maximum input voltage |
265
Vac |
| Minimum input voltage |
Adjustable
threshold from 150 to 230 Vac |
| Input frequency |
45
- 65 Hz |
| Power Factor
Correction (PFC) |
EN
61000-3-2 |
| PDF file |
See PDF file |
See PDF file |
See PDF file |
See PDF file |
| Technical Data |
HPC 2800-12 |
HPC 4400-24 |
HPC 6000-48 |
HPC 8000-48 |
| General Data |
Multifunction contact -
potential free (3 points) |
16
A - 250 Vac |
| Max. current on transfer relay |
30 A / 6.9 kVA |
30 A / 6.9 kVA |
30 A / 6.9 kVA |
50 A / 11.5 kVA |
| Transfer time |
<
20 ms |
| Weight |
33 kg |
39 kg |
41 kg |
45 kg |
| Dimensions L x W x H (mm) |
480 x 288 x 242 |
480 x 288 x 242 |
480 x 288 x 242 |
500 x 288 x 242 |
| IP protection index |
IP
20 |
| EEC conformity |
EN50081
I/II, EN 55014 - EN 55022, EN 61000-3-2 IEC 801 I/II/III/IV,
CEI 555, IEC 1000-3-2, LVD 73/23/EEC |
| Working range |
-20
to 55ºC |
| Ventilation |
from
45ºC |
| Acoustic level
without / with ventilation |
<
10 dB / <35dB |
| Recommended battery capacity (C10) |
>
5 x Pnom / Unom |
| Warranty |
2
years |
| PDF file |
See PDF file |
See PDF file |
See PDF file |
See PDF file |
| Optional Extras for HP Range |
| Remote control |
| Remote power sharing |
| Battery temperature
sensor |
Studer Xtender Inverter Charger
The Studer Xtender
will meet the expectations and the needs of the solar, mobile and backup
markets.This new range of Inverter-Chargers is now available using Digital Signal
Processor(DSP) Technology. The Xtender Series consists of 4 products starting at 2500va through to 4000va,
5000va and 7000VA.
The Xtender range is now available.The main features of the
Xtender series are the inverter, battery charger and transfer system.
These functions can be combined and controlled in a totally automatic mode providing an exceptional optimisation and management of the available energy resource.
The function Smart-Boost offers the possibility to assist the source with the function Smart-Boost. This
enables the user to add the inverter power to another source,such as a genset or
shorepower, even in case of special loads (inductive, asymetrical, high crest factor).
The Power Increase option with the implementation of several units,offers the user a 3-phase source or to configure the units
in parallel (up to 3) to increase the power available. Up to 9 inverters of the Xtender series can shall be linked together.
It is also possible to add an Xtender to almost any existing inverter and thus increase the
power availableStuder Xtender Inverter Charger

- Pure Sinewave Inverter range from 3000VA to
8000VA
- 6 Stage Fully Automatic Charger adjustable
from 0-140A
- Optional Remote Control & RCC 02
- High Quality 2 Year Warranty
Studer XPC Inverter Charger

Studer XPC Inverter Charger
- Pure Sinewave Inverter range from 1100W to
1600W
- 4 Stage Fully Automatic Charger adjustable
from 0-45A
- Optional Built-in Solar Charge controller
- Optional Remote Control
- High Quality 2 Year Warranty
| Technical Data |
XPC1400-12 |
XPC2200-24 |
XPC2200-48 |
| Inverter |
| Nominal battery voltage |
12V |
24V |
48V |
| Input voltage range |
9.5 - 16 V |
19 - 32 V |
38 - 64 V |
| Continuous power @ 25°C |
1100VA |
1600VA |
1600VA |
| Power 30 min. @ 25°C |
1400VA |
2200VA |
2200VA |
| Maximum power load 5 sec. |
3 x Pnom |
| Maximum load |
up to short
circuit |
| Maximum asymmetric load |
up to Pcont. |
| Stand-by adjustment |
1 to 25W |
| Cos |
0.1 - 1 |
| Maximum efficiency |
94% |
95% |
| Consumption OFF/Stand-by/ON |
0.5/0.6/4W |
0.8/0.9/7W |
1.2/1.3/7W |
| Output voltage |
230Vac (- 10% / 0) |
| Output frequency crystal controlled |
50Hz +/- 0.05% |
| Total harmonic distortion |
< 4% |
< 2% |
| Dynamic behaviour on load change 0 to 100% |
0.5 ms |
| Overload and short circuit protection |
Automatic disconnection with
3 time restart attempt |
| Overheat protection |
Acoustic warning before shut-off
- with automatic restart |
| PDF file |
See PDF
file |
See PDF
file |
See PDF
file |
| Technical Data |
XPC1400-12 |
XPC2200-24 |
XPC2200-48 |
| Battery charger (4 STEP) I-U-Uo-Equalise
(every 25 cycles) |
| Charging current adjustable |
0 - 45 A |
0 - 37 A |
0 - 20 A |
| Input current
balance adjustment (Power Sharing) |
n.a. |
| Maximum input voltage |
265Vac |
| Minimum input voltage |
Adjustable threshold from 150
to 230Vac |
| Input frequency |
45 - 65Hz |
| Power Factor Correction (PFC) |
EN 61000-3-2 |
| PDF file |
See PDF
file |
See PDF
file |
See PDF
file |
| Technical Data |
XPC1400-12 |
XPC2200-24 |
XPC2200-48 |
| Optional solar charger (4 stages)
I-U-Uo-Equalize (every 25 cycles) |
| Maximum PV open circuit voltage
(V) |
25 V |
45 V |
90 V |
| Maximum charge current (A) |
30 A |
30 A |
20 A |
| Working principle: I-U-Uo-Equalize
(every 25 cycles) |
Shunt |
| PDF file |
See PDF
file |
See PDF
file |
See PDF
file |
| Technical Data |
XPC1400-12 |
XPC2200-24 |
XPC2200-48 |
| Battery control (thresholds and
times adjustable by the user) |
| Absorption time |
0-4 h |
| End charge cycle voltage |
14.4V |
28.8V |
57.6V |
| Floating voltage |
13.6V |
27.2V |
54.4V |
| Equalization voltage |
15.6V |
31.2V |
62.4V |
| Deep-discharge protection |
10.8V |
21.6V |
43.2V |
| Temperature compensation (optional
CT-35) |
-3mV / o C / cell |
| PDF file |
See PDF
file |
See PDF
file |
See PDF
file |
| Technical Data |
XPC1400-12 |
XPC2200-24 |
XPC2200-48 |
| General data |
| Multifunction contact - potential
free (3 points) |
16A - 250Vac |
| Max. current on transfer relay |
16A/3.7kVA |
16A/3.7kVA |
16A/3.7kVA |
| Transfer time |
< 20 ms |
| Weight |
11.7 kg |
12.6 kg |
| Dimension h x l x L [mm] |
124x215x410 |
| Protection index
IP20 |
IP23 with top
cover CxxxxIP23 |
| EC conformity |
EN 61000-6-1, EN 61000-6-3, EN
55014, EN 55022, EN
61000-3-2, Dir. 89/336/EEC, LVD 73/23/EEC |
| Operating temperature range |
-20 to 55 oC |
| Ventilation |
from 45 oC |
| Acoustic level without / with
ventilation |
< 10 dB / < 35 dB |
| PDF file |
See PDF
file |
See PDF
file |
See PDF
file |
| Optional Extras
for XPC Range |
| Solar charge controller |
XPC xxxx-S |
| Remote control (112 x 138 x 25mm / 20 m
cable) |
RCC-01 |
| IP-23 top cover |
C-IP23 |
| AC cable cover |
CFC-01 |
| Battery temperature sensor
(58 x 51.5 x 22mm / 3 m
cable) |
CT-35 |
Trade Buyers
| Corporate Buyers | Individual
Buyers | Contact us
All products and prices are subject to change and availability without
prior notification.
solenttech.co.uk ©
|